10-40 kVA Three Phase, On-Line Double Conversion, Uninterruptable Power System

FirstLine PLT

10-60 kVA
Three Phase, On-Line Double Conversion, Uninterruptible Power Supply

In the event of an AC power failure, the FirstLine® PLT UPS will automatically transfer to battery power and continue to provide power without any interruption for the full amount of time you select. When power returns, the FirstLine® PLT UPS will automatically recharge the batteries for the next unexpected power outage or disturbance.

 


  • Up to 94% Efficient
    • Lower energy costs and carbon footprint
  • Compact & Reliable
    • 10-60 kVA internal batteries allow smaller footprint
    • Cooler operation extends internal component life
  • AC Input Performance
    • High input power factor of 0.99
    • Low input current distortion of <= 1% (THDi) @ full load
    • Soft Start Power walk-in function that ensures progressive rectifier start-up
  • IGBT and Digital Signal Processor (DSP)
    • Reduces the impact of the UPS on the local supply
    • Simplifies installation where there is limited power capacity
  • Dual Input
    • Main power and secondary emergency standby power increase resilience of single or parallel system configuration
  • Adaptive Feed Cancellation
    • Advanced control with AFC forward cancellation technology for low harmonic distortion
  • Menu Select Display
    • User friendly display is easy to see and intuitive to use
  • Parallel up to 4 Units
    • Provides redundancy for mission critical applications with no additional hardware
    • Parallel Kit, Communication through CANBUS Parallel Card
  • Operates as a precision Power Conditioner
    • -0 models can operate as a Power Conditioner upgradeable to a UPS in the future
  • Frequency Conversion
    • All units can be set as a 50/60 hZ Frequency Converter
  • Nationwide Service Program
    • Factory trained service personnel maximize equipment life
    • Full start-up service & preventive maintenance lowers cost of ownership
  • Full Two Year Warranty
  • Medical
  • Data Centers
  • Industrial Facilities
  • Education
  • Government

*For more detailed application information, please refer to the following document: Application Drawings and Notes

Product Selector | Firstline PLT

Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 408
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 408
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 408
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 950
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 950
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 950
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 735
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 735
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 735
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 630
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 630
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 47.1 x 20.3 x 33
Weight (lbs.): 630
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 659
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 659
Load kVA: 10
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1209
Load kVA: 10
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1164
Load kVA: 10
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1154
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1114
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1154
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1230
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1240
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1770
Battery Runtime @ 100% Load (Internal): 90
Load kVA: 10
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1464
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1419
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1409
Battery Runtime @ 100% Load (Internal): 35
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1369
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1409
Battery Runtime @ 100% Load (Internal): 35
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 996
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1302
Battery Runtime @ 100% Load (Internal): 44
Load kVA: 10
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1354
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1309
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1299
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1259
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1299
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 10
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1033
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1319
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1274
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1264
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1224
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 10
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1264
Battery Runtime @ 100% Load (Internal): 9
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 659
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 659
Load kVA: 15
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1183
Load kVA: 15
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1179
Load kVA: 15
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1232
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1088
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1232
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1206
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1206
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1770
Battery Runtime @ 100% Load (Internal): 53
Load kVA: 15
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1438
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1434
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1487
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1343
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1487
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 965
Battery Runtime @ 100% Load (Internal): 11
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1270
Battery Runtime @ 100% Load (Internal): 27
Load kVA: 15
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1688
Battery Runtime @ 100% Load (Internal): 11
Load kVA: 15
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1684
Battery Runtime @ 100% Load (Internal): 11
Load kVA: 15
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1737
Battery Runtime @ 100% Load (Internal): 10
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1593
Battery Runtime @ 100% Load (Internal): 11
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1737
Battery Runtime @ 100% Load (Internal): 10
Load kVA: 15
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 867
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 15
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1293
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 15
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1289
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 15
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1342
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1198
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 15
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HRL1234W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1342
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 690
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 700
Load kVA: 20
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1493
Load kVA: 20
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1529
Load kVA: 20
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1332
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1292
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1332
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1230
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1240
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1770
Battery Runtime @ 100% Load (Internal): 36
Load kVA: 20
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1743
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 20
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1779
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 20
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1582
Battery Runtime @ 100% Load (Internal): 14
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1542
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1582
Battery Runtime @ 100% Load (Internal): 14
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 996
Battery Runtime @ 100% Load (Internal): 7
Load kVA: 20
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1302
Battery Runtime @ 100% Load (Internal): 18
Load kVA: 20
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1993
Battery Runtime @ 100% Load (Internal): 7
Load kVA: 20
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 2029
Battery Runtime @ 100% Load (Internal): 7
Load kVA: 20
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1832
Battery Runtime @ 100% Load (Internal): 6
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1792
Battery Runtime @ 100% Load (Internal): 7
Load kVA: 20
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1832
Battery Runtime @ 100% Load (Internal): 6
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1125
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1125
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1125
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 690
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 700
Load kVA: 30
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1319
Load kVA: 30
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1323
Load kVA: 30
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1495
Load kVA: 30
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1243
Load kVA: 30
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1495
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1230
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1240
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1770
Battery Runtime @ 100% Load (Internal): 21
Load kVA: 30
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1569
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1573
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1745
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1493
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1745
Battery Runtime @ 100% Load (Internal): 8
Load kVA: 30
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1270
Battery Runtime @ 100% Load (Internal): 11
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 584
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1185
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1185
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 52 x 23.20 x 33
Weight (lbs.): 1185
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 690
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 700
Load kVA: 40
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1416
Load kVA: 40
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1455
Load kVA: 40
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1639
Load kVA: 40
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1294
Load kVA: 40
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: NO BATTERY
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1639
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1230
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1240
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1770
Battery Runtime @ 100% Load (Internal): 15
Load kVA: 40
Input Voltage: 208
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1666
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 480
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1705
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 480
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1889
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 40
Input Voltage: 480Y/277
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1544
Battery Runtime @ 100% Load (Internal): 5
Load kVA: 40
Input Voltage: 480Y/277
Output Voltage: 480Y/277
Internal Maintenance Bypass: Yes
Internal Batteries: HR1290W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1889
Battery Runtime @ 100% Load (Internal): 4
Load kVA: 40
Input Voltage: 208Y/120
Output Voltage: 208Y/120
Internal Maintenance Bypass: Yes
Internal Batteries: HR1251W
Dimensions (H" x W" x D"): 72.4 x 23.1 x 34.5
Weight (lbs.): 1270
Battery Runtime @ 100% Load (Internal): 7

Choose Your Location